NUT (Network UPS Tools)

Networking 2026-10-10

NUT monitors uninterruptible power supplies, power distribution units, automatic transfer switches and solar controllers, and triggers a graceful system shutdown when the battery runs out. It is pre-installed on Shani OS.

About the change (2026-10-10): this page used to describe apcupsd, which ShaniOS shipped before. apcupsd has had no upstream release since 3.14.14 (2016/2017) — Arch still ships that version, repackaged nine times with the code unmoved. NUT is at 2.8.5, its data model is published as IETF RFC 9271, it covers 170+ manufacturers over serial, USB, SNMP and IPMI, and it ships an apcupsd-ups driver that still reaches apcupsd-controlled hardware, so nothing that worked before is lost.

Active by default, with nothing to monitor yet. ShaniOS starts the NUT stack on a fresh install — MODE=standalone with ALLOW_NO_DEVICE=true — so a UPS you plug in later is picked up without you enabling anything. Until then it reports that no device is configured, which is the honest answer rather than a fault.


Find your UPS

sudo nut-scanner -U

This discovers USB, serial, SNMP, NetXML and IPMI devices and prints a complete, ready-to-paste section naming the driver and port your hardware actually needs. That is the step to do first: which protocol a UPS speaks is a fact about the device, and a wrong value fails as a driver that exits silently rather than as an error you can see.

Copy the section it prints into /etc/nut/ups.conf:

[myups]
    driver = usbhid-ups
    port = auto
    desc = "local UPS"

Then restart the stack:

sudo systemctl restart nut-server.service nut-monitor.service

What happens when the power goes

/etc/nut/upsmon.conf holds the policy. This is a directive file — KEY value per line, no = and no sections — which is a different shape from the INI-like ups.conf and upsd.users beside it.

MONITOR myups@localhost 1 monuser <password> master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
POWERDOWNFLAG /etc/killpower
DEADTIME 15
POLLFREQ 5
POLLFREQALERT 5
FINALDELAY 0
KeyWhat it does
MONITORwhich UPS to watch. The form is `system powervalue user password (master\secondary)`. Five values after the key — a short line is a syntax error to upsmon and the UPS is never monitored.
MINSUPPLIEShow many supplies must be on battery before shutdown starts. 0 is accepted and can then never fire.
SHUTDOWNCMDthe command that brings the machine down. Quote it: unquoted, only its first word is a command and the rest become arguments nothing reads.
POWERDOWNFLAGthe flag file telling the driver to cut UPS power once the machine is down.
DEADTIMEseconds of no answer before the UPS counts as gone. When it fires, upsmon treats that as on-battery, because an unreachable UPS is indistinguishable from a dead one.
POLLFREQ / POLLFREQALERTseconds between checks on mains and on battery. The battery value is the more useful one to lower.
FINALDELAYseconds between running SHUTDOWNCMD and upsmon exiting.

There is no battery-percentage shutdown threshold. This is the one thing apcupsd had that NUT does not, and it is worth knowing before you look for it: upsmon responds to the UPS hardware's own low-battery signal, so you cannot set "shut down at 15%". Getting a charge- or runtime-based trigger instead needs dummy-ups with overridden battery.charge/battery.runtime values plus upssched, which is a deliberate advanced setup rather than a default.

Setting the policy from the window

ShaniOS' Cassini settings manager has a UPS page that edits exactly these keys, checks each one before it is written, and tells you a restart is needed — apcupsd and NUT both read their configuration once at startup.


Status

upsc myups@localhost              # everything NUT reports, as it reports it
systemctl status nut-monitor.service

Key fields in upsc output:

FieldMeaning
ups.statusOL on line, OB on battery, LB low battery
battery.chargecharge as a percentage
battery.runtimeestimated remaining runtime in seconds
ups.loadload on the UPS
input.voltagemains voltage
battery.voltagebattery voltage

Files and who owns them

FileWhat it holdsEdit it?
/etc/nut/ups.confthe device — driver, port, descyes, or let nut-scanner -U write it
/etc/nut/upsmon.confthe shutdown policyyes
/etc/nut/upsd.confwhere the data server listens. ShaniOS ships it bound to 127.0.0.1 only.only with care — see below
/etc/nut/upsd.usersthe monitor credentialno — see below
/etc/nut/nut.confwhich NUT layers run. ShaniOS ships MODE=standalone.no

upsd.users is not editable and is not shown. It holds the credential that can issue a forced shutdown of the UPS. ShaniOS generates it once per install in its packaging hook, rather than shipping a fleet-wide value that would be one password able to power down every machine's UPS.

upsd.conf ships bound to loopback only, and the same reasoning applies: the monitor user can force a power-down, so reachable network plus a guessable password is a remote power-off primitive. NUT's own calls that mode netserver and notes it "is opened to the network [so] a special care should be applied to security concerns". If a second machine ever needs to monitor this UPS, that is a deliberate change, not a LISTEN widened for convenience.


Multi-machine monitoring

ShaniOS runs NUT in standalone mode — one UPS, one machine. NUT also supports netserver (share this UPS with other machines) and netclient (watch a UPS somewhere else). Both are documented in nut.conf and both are opt-in, because the first opens a network service and the second depends on one.